Permit Number: T06CM00022
Parcel: Unknown

Review Status: Completed

Review Details: POST 3RD PARTY REVIEW

Permit Number - T06CM00022
Review Name: POST 3RD PARTY REVIEW
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/18/2006 ROBERT SHERRY WATER REVIEW Approved
01/18/2006 JIM EGAN FIRE REVIEW Denied 1. Fire sprinklers required for Areas "A" and "B" per 2003 IBC Sec. 412.2.6. (Areas "A" & "B" limitted to 5000 sq. ft. for Type 5-B construction.)
2. Provide details and verification to indicate vertical continuity of "2-hour fire wall" in accordance with 2003 IBC Sec.705.6.
3. Show locations of fire hydrants on plan.
4. Plans must be returned to Third Party reviewer for approval.
01/19/2006 GERRY KOZIOL WWM REVIEW Denied needs wastewater 8th floor review connecting to exsisting on-site private sewer (sharing w/ 1732 E VAlencia? and future hanger A2 & A4 )

Final Status

Task End Date Reviewer's Name Type of Review Description
01/26/2006 JMORALE1 OUT TO CUSTOMER Completed
01/26/2006 SUE REEVES REJECT SHELF Completed