Permit Review Detail
Review Status: Completed
Review Details: POST 3RD PARTY REVIEW
Permit Number - T06CM00022
Review Name: POST 3RD PARTY REVIEW
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
01/18/2006 | ROBERT SHERRY | WATER | REVIEW | Approved | |
01/18/2006 | JIM EGAN | FIRE | REVIEW | Denied | 1. Fire sprinklers required for Areas "A" and "B" per 2003 IBC Sec. 412.2.6. (Areas "A" & "B" limitted to 5000 sq. ft. for Type 5-B construction.) 2. Provide details and verification to indicate vertical continuity of "2-hour fire wall" in accordance with 2003 IBC Sec.705.6. 3. Show locations of fire hydrants on plan. 4. Plans must be returned to Third Party reviewer for approval. |
01/19/2006 | GERRY KOZIOL | WWM | REVIEW | Denied | needs wastewater 8th floor review connecting to exsisting on-site private sewer (sharing w/ 1732 E VAlencia? and future hanger A2 & A4 ) |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
01/26/2006 | JMORALE1 | OUT TO CUSTOMER | Completed |
01/26/2006 | SUE REEVES | REJECT SHELF | Completed |