Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Active
Review Details: OTHER
Permit Number - T06BU02824
Review Name: OTHER
Review Status: Active
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 02/21/2007 | CHRISTY FOREMAN | BUILDING-COMMERCIAL | REVIEW | Denied | CITY OF TUCSON DEVELOPMENT SERVICES STRUCTURAL REVIEW COMMENTS DATE: 2/21/07 ACTIVITY NUMBER: T06BU02818, T06BU02819, T06BU02820, T06BU02821, T06BU02822, T06BU02823, T06BU02824 PROJECT NAME: Balcony Rails PROJECT ADDRESS: 901 N Euclid Ave ARCHITECT / ENGINEER: L2 Architects PROJECT REVIEWER: Christy Foreman TRANSMIT ORIGINAL DRAWINGS WITH NEXT SUBMITTAL. PLEASE CALL AT 791-5550 X1108 OR EMAIL AT CHRISTY.FOREMA1@TUCSONAZ.GOV IF YOU CARE TO DISCUSS. 1) Provide structural calculations per section 1607.7.1, IBC 2003. Handrails and guards shall be designed to resist a load of 50 plf applied at any direction and to transfer this load through the supports to the structure. This is the load required to be used for a R2 occupancy the load that was justified was for one & two family dwellings. 2) Clarify barrier height per section 1012.2, IBC 2003. |