Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

The login landing page when selecting 'View' is still occurring and is still pending further investigation. 

Permit Number: T06BU02818
Parcel: 115046430

Address:
901 N EUCLID AV

Review Status: Active

Review Details: OTHER

Permit Number - T06BU02818
Review Name: OTHER
Review Status: Active
Review Date Reviewer's Name Type of Review Description Status Comments
02/21/2007 CHRISTY FOREMAN BUILDING-COMMERCIAL REVIEW Denied CITY OF TUCSON DEVELOPMENT SERVICES
STRUCTURAL REVIEW COMMENTS

DATE: 2/21/07
ACTIVITY NUMBER: T06BU02818, T06BU02819, T06BU02820, T06BU02821, T06BU02822, T06BU02823, T06BU02824
PROJECT NAME: Balcony Rails
PROJECT ADDRESS: 901 N Euclid Ave
ARCHITECT / ENGINEER: L2 Architects
PROJECT REVIEWER: Christy Foreman


TRANSMIT ORIGINAL DRAWINGS WITH NEXT SUBMITTAL.

PLEASE CALL AT 791-5550 X1108 OR EMAIL AT CHRISTY.FOREMA1@TUCSONAZ.GOV IF YOU CARE TO DISCUSS.

1) Provide structural calculations per section 1607.7.1, IBC 2003. Handrails and guards shall be designed to resist a load of 50 plf applied at any direction and to transfer this load through the supports to the structure. This is the load required to be used for a R2 occupancy the load that was justified was for one & two family dwellings.
2) Clarify barrier height per section 1012.2, IBC 2003.

Final Status

Task End Date Reviewer's Name Type of Review Description
01/16/2007 ANY REJECT SHELF RECEIVED