Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T06BU02479
Parcel: 11805020A

Review Status: Completed

Review Details: GRADING

Permit Number - T06BU02479
Review Name: GRADING
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/29/2006 JASON GREEN ENGINEERING REVIEW Denied DATE: November 30, 2006
SUBJECT: 1202 S Camino Del Sierra- Culvert Installation
TO: Jeff Dana
LOCATION: T14S R13E Sec22, Ward 1
REVIEWERS: Jason Green, CFM
ACTIVITY: T06BU02479 (Grading Plan) and T06OT02675 (Floodplain Use Permit)


SUMMARY: Engineering Division of Development Services Department has received and reviewed the grading plan, Floodplain Use Permit and the submitted Drainage Statement, prepared by Stantec Consulting Inc., dated August 4, 2006, for the above referenced property. Engineering Division does not recommend approval of the grading plan, Floodplain Use Permit, or drainage statement at this time. Please provide the following for further review:

1. The HEC-RAS profile sheets can not be reviewed until the drainage statement provides all required hydrology information. The Watershed Map, Fig.2.1, and the associated hydrology calculations were not included in the submitted report.

2. Provide a revised drainage statement verifying the watershed map and hydrology calculation sheets for the associated drainage area for the unnamed wash. Label the topography, direction of flow, subject parcels and delineated watershed. Show on the watershed maps the entire delineated watershed used for the hydrologic and hydraulic calculations.

3. Provide verification for the 264 cfs discharge value used for the hydraulic calculations.

4. Revise the typographical error in the second paragraph of the introduction section to reference the proper FEMA FIRM Map Panel number.


GENERAL COMMENTS:

Please provide a revised drainage statement for review and approval that address the comments provided above. Include a comprehensive response letter addressing in detail responses to all of the above comments.

If you have any questions, or to schedule a meeting, I can be reached at 791-5550, extension 1189.



Jason Green, CFM
Senior Engineer Associate
Engineering Division
Development Services

Final Status

Task End Date Reviewer's Name Type of Review Description
12/01/2006 DELMA ROBEY OUT TO CUSTOMER Completed
12/01/2006 SUE REEVES REJECT SHELF Completed