Review Details: RESUBMITTAL - GRADING ALL
Permit Number - T06BU02375
Review Name: RESUBMITTAL - GRADING ALL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 03/15/2007 | PATRICIA GILBERT | ENGINEERING | REVIEW | Approved | |
| 03/20/2007 | DAVID RIVERA | ZONING | REVIEW | Denied | 03/20/07 Development Services Department Zoning Review Section David Rivera Principal Planner Comments: 1. The grading plan has been reviewed by Zoning Review Section but cannot approve the plan until the following zoning comments are addressed. a. The grading plan does not match the approved development plan. Please revise the grading plan as required. b. Draw both the outdoor dining area and draw the handicapped access ramp for the handicapped parking space. c. Label the maximum allowed slope for the handicapped parking spaces and access aisles. Per ANSI 503.4, the maximum allowed slope is 1:48 (2%). The slope may labeled on the H.C. parking detail drawing. d. Draw and label the bicycle parking faqility on the grading plan as approved on the development plan. e. Add a detail drawing that depicts the truncated domes and demonstrates compliance with ANSI section 406.12 and 406.13 2. Zoning will re-review the grading plan on the next submittal to ensure compliance with the approved site/development plan. Additional comments may be forthcoming. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 03/23/2007 | FSANCHE1 | OUT TO CUSTOMER | Completed |
| 03/23/2007 | SUE REEVES | REJECT SHELF | Completed |