Permit Number: T06BU02304
Parcel: 11007412C

Review Status: Completed

Review Details: RESUBMITTAL - GRADING ALL

Permit Number - T06BU02304
Review Name: RESUBMITTAL - GRADING ALL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/16/2007 SUZANNE BOHNET ENGINEERING REVIEW Denied Grading plan cannot be approved until the Site Plan is approved.

Grading Plan:
1. The Site Plan states "Existing Chain Link Fence to Remain" for the southern boundary of the proposed development. The Grading Plan states "Existing Chain Link Fence to be removed, Proposed 6' High CMU Screenwall". Additionally, the responses to initial review comments state the CMU wall is to meet the existing chain link fence at the southwest corner. Please revise the Site Plan to be in agreement with the Grading Plan.
2. Please clarify that the designed drainage holes for the block wall are to be located only along the proposed southern wall and not the eastern wall.

Additional comments may be forthcoming after the retention requirements are shown on the Grading and Site Plan.
12/18/2006 STEVE SHIELDS ZONING REVIEW Denied DSD TRANSMITTAL

FROM: Steve Shields
Lead Planner

PROJECT: 2552 N. Alvernon Way - Office Building
T06CM02304
Grading Plan (2nd Review)

TRANSMITTAL DATE: December 19, 2006

1. The grading plan has been reviewed by Zoning Review Section but cannot approve the plan until it has been approved by the Engineering, and Landscape Review Sections and until all zoning comments or concerns have been addressed.

2. Zoning could not verify that the grading plan was in compliance with the approved site plan. Please submit two copies of the approved and stamped site, landscape, and NPPO plans with the next grading plan submittal.

3. Zoning will re-review the grading plan on the next submittal to insure compliance with the approved and stamped site plan. Additional comments may be forthcoming.

If you have any questions about this transmittal, please contact me at Steve.Shields@tucsonaz.org or (520) 791-5608 ext. 1180.

C:\planning\grading\t06bu02304.doc

RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Approved site plan and additional requested documents
12/29/2006 ANDREW CONNOR NPPO REVIEW Denied Site plan approval is necessary to continue review.

Final Status

Task End Date Reviewer's Name Type of Review Description
01/29/2007 CINDY AGUILAR OUT TO CUSTOMER Completed
01/29/2007 SUE REEVES REJECT SHELF Completed