Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T06BU02269
Parcel: 11011369B

Address:
4881 E GRANT RD

Review Status: Completed

Review Details: RESUBMITTAL - GRADING ALL

Permit Number - T06BU02269
Review Name: RESUBMITTAL - GRADING ALL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/01/2006 DAVID RIVERA ZONING REVIEW Denied 11/01/06

Development Services Department
Zoning Review Section

David Rivera
Principal Planner

Comments:

1. The grading plan has been reviewed by Zoning Review Section but cannot approve the plan until it has been approved by the Engineering, and Landscape Review Sections.

2. Zoning will re-review the grading plan on the next submittal. If both Engineering and Landcsape reviewers approve the grading plan, Zoning is willing to review and approve the grading plan over the counter with an appointment. Please cal either Michael St. Paul or myself and setup an appointment if this turns out to be the case.
11/16/2006 ANDREW CONNOR NPPO REVIEW Approved
12/01/2006 LOREN MAKUS ENGINEERING REVIEW Denied 1. The Stormwater Pollution Prevention Plan must be certified by the operator.
2. Provide Four copies of the grading plan and three copies of the SWPPP.
3. Revise general note 2 to indicate that all work will conform to the grading development standard. City of Tucson Development Standard 11-01.
4. Provide dimensions on the plan for PAALs, islands, sidewalks, and parking spaces.
5. The approved development plan indicates the use of scuppers throughout the site. Provide details and locations of these and other drainage structures on the grading plan.

Final Status

Task End Date Reviewer's Name Type of Review Description
12/11/2006 DELMA ROBEY OUT TO CUSTOMER Completed
12/11/2006 SUE REEVES REJECT SHELF Completed