Permit Number: T06BU02252
Parcel: 10824012B

Address:
2550 E RIVER RD

Review Status: Completed

Review Details: POOL:COMM-MODEL

Permit Number - T06BU02252
Review Name: POOL:COMM-MODEL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/28/2006 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Provide plans sealed by an Arizona Registrant.
2. Revise the font size used on the drawings to a minimum of 1/8-inch (all upper case). Reference Section 302.3, Uniform Administrative Code, 1997.
3. Provide construction documents drawn to scale and with sufficient detail and clarity to demonstrate that the work complies with the applicable plumbing codes, ANSI/NSPI-1 2003, and with ANSI/NSPI-2 2003. Reference Section 302.3, Uniform Administrative Code, 1997.
4. If the utilities (e.g. water, natural gas, and sewer) are provided by others under separate permits, provide reference drawings to show the locations and capacities of the utilities.
09/28/2006 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Provide plans sealed by an Arizona Registrant.
2. Provide construction documents drawn to scale and with sufficient detail and clarity to demonstrate that the work complies with the applicable codes. Reference Section 302.3, Uniform Administrative Code, 1997.
3. Revise the font size used on the drawings to a minimum of 1/8-inch (all upper case). Reference Section 302.3, Uniform Administrative Code, 1997.
10/19/2006 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied 1. Provide full electrical design for all pool and spa equipment, and any additional lighting, sealed by an Arizona Registrant.
2. Revise the font size used on the drawings to a minimum of 1/8-inch (all upper case). Reference Section 302.3, Uniform Administrative Code, 1997.
3. Provide construction documents drawn to scale and with sufficient detail and clarity to demonstrate that the work complies with the NEC, IECC, and Tucson Lighting Code.
10/20/2006 LINHART PETERSEN POERS ASSOC. BUILDING-COMMERCIAL REVIEW Denied 1)Provide Enginneered Structural Plans/Calculations.
2)No structural review could be performed as no structural plans or calculations were provided

Final Status

Task End Date Reviewer's Name Type of Review Description
11/16/2006 BETH GRANT OUT TO CUSTOMER Completed
11/16/2006 SUE REEVES REJECT SHELF Completed