Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Number: T06BU02243
Parcel: 13409015G

Review Status: Completed

Review Details: GRADING

Permit Number - T06BU02243
Review Name: GRADING
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/18/2007 ANY ENGINEERING REVIEW Approved
01/25/2007 ANDREW CONNOR NPPO REVIEW Approv-Cond
01/31/2007 MICHAEL ST. PAUL ZONING REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
03/10/2008 SUE REEVES APPROVAL SHELF Completed
03/10/2008 VFLORES1 OUT TO CUSTOMER Completed