Review Details: GRADING
Permit Number - T06BU02127
Review Name: GRADING
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 08/30/2006 | ANDREW CONNOR | NPPO | REVIEW | Denied | Submit a copy of the approved site plan including, landscape and native plant preservation plans for reference. The grading application will be reviewed for compliance only when the approved documents are included in the submittal. Revise grading plans as necessary to comply with the approved site plan. |
| 09/21/2006 | DAVID RIVERA | ZONING | REVIEW | Denied | 09/21/06 Development Services Department Zoning Review Section David Rivera Principal Planner Comments: 1. The grading plan has been reviewed by Zoning Review Section but cannot approve the plan until it has been approved by the Engineering, and Landscape Review Sections and until all zoning comments or concerns have been addressed. 2. Zoning could not verify that the grading plan was in compliance with the approved site plan. Please submit two copies of the approved and stamped site, landscape, and NPPO plans with the next grading plan submittal. 3. Zoning will re-review the grading plan on the next submittal to ensure compliance with the approved and stamped site plan. Additional comments may be forthcoming. |
| 09/25/2006 | PAUL MACHADO | ENGINEERING | REVIEW | Denied | To: Dinkar Gangwal, P.E. DATE: September 27, 2006 Alpha Engineering 117 N. Sixth Ave. Tucson, Arizona 85701 SUBJECT: Golf Links Comm. Bldg., 7755 E Golf Links Rd. Grading Plan T06BU02127 (First Review) T14S, R15E, Section 29 RESUBMITTAL REQUIRED: Grading Plan, Drainage Report The Grading Plan (GP) and Drainage Report (DR) cannot be approved as submitted. Please address the following review comments prior to the next submittal. Grading Plan: 1. Please include a response letter to the comments along with the corrected copies of the GP. 2. Per the site plan comment, sidewalks will be required along the entire length of all street frontages. This includes but not limited to upgrading the existing W/C ramps to meet current code per D.S. 3-01.2.4.3.A. 3. List administrative address/site address on plans. 4. List Grading plan number (T06BU02127) on each sheet. 5. Provide a Location Map (3" = 1 mile) 6. Please show the proposed roof drainage patterns, 100% of the 10-year flow must be conveyed under the sidewalks. Please provide supporting calculations to demonstrate compliance with D.S. 3-01.4.4. If the location(s) of the roof scuppers have not yet been decided, add a general note indicating sidewalk scuppers (per COT/SD) will be used when the roof scuppers locations have been designed. 7. A permit or a private improvement agreement will be necessary for any work performed within the Right-of-way. Contact Permits and Codes at (520) 791-5100 for permit information. 8. Show the 100-year flood peak discharge. 9. Call out peak discharges entering and exiting the site. Drainage report: 1. The DR has been accepted by engineering. If you have any questions, I can be reached at 791-5550 x1193 or Paul.Machado@tucsonaz.gov Paul P. Machado Senior Engineering Associate City of Tucson/Development Services Department 201 N. Stone Avenue P.O. Box 27210 Tucson, Arizona 85726-7210 (520) 791-5550 x1193 office (520) 879-8010 fax 7755 E Golf Links Rd. grad. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 10/20/2006 | DELMA ROBEY | OUT TO CUSTOMER | Completed |
| 10/20/2006 | SUE REEVES | REJECT SHELF | Completed |