Permit Number: T06BU02100
Parcel: Unknown

Address:
152 W ELVIRA RD

Review Status: Completed

Review Details: GRADING

Permit Number - T06BU02100
Review Name: GRADING
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/30/2006 ANDREW CONNOR NPPO REVIEW Denied Submit a copy of the approved landscape and native plant preservation plans for reference. The grading application will be reviewed for compliance only when the approved documents are included in the submittal. Revise grading plans as necessary to comply with the approved plans.
09/21/2006 DAVID RIVERA ZONING REVIEW Denied 09/21/06

Development Services Department
Zoning Review Section

David Rivera
Principal Planner

Comments:

1. The grading plan has been reviewed by Zoning Review Section but cannot approve the plan until it has been approved by the Engineering, and Landscape Review Sections and until all zoning comments or concerns have been addressed.

2. Zoning could not verify that the grading plan was in compliance with the approved Final Plat development plan. Please submit one copy of the CDRC approved and development plan sheets, landscape, and NPPO plans with the next grading plan submittal.

3. Zoning will re-review the grading plan on the next submittal to ensure compliance with the CDRC approved development plan sheets. Additional comments may be forthcoming.
10/16/2006 LOREN MAKUS ENGINEERING REVIEW Denied October 16, 2006
TO: Lloyd Rogers, PE
SUBJECT: Grading Plan: Elstone II Subdivision
REVIEWER: Loren Makus
ACTIVITY NUMBER: T06BU02100

SUMMARY: The Grading Plans were reviewed by Development Services Department, Engineering Division on December 2, 2005. They were not approved at this time.
1. The submitted plans seem to be copies of the paving and public improvement plans. Provide a complete grading plan submittal.
2. Revise the title blocks for each sheet of the Grading Plan to clearly identify the plan. Remove references to the City of Tucson Department of Transportation.
3. Provide the appropriate general notes for the grading plan.
4. Provide general dimensions for all of the basins and other drainage features. This is necessary so the inspectors can effectively inspect the site. They often must use photo-reproductions that are not scaleable.
5. The cut and fill quantities on the grading plan do not appear consistent with the existing and proposed grades. Provide consistent cut and fill quantities.
6. Provide a complete Stormwater Pollution Prevention Plan. Include a completed copy of the ADEQ checklist with the SWPPP to ensure that all of the requirements have been met. The checklist is available on the ADEQ stormwater web site.

If you have any questions or if you wish to discuss any of these comments, I can be reached at 520.791-5550 ext. 1161 or by email at loren.makus@tucsonaz.gov.
Loren Makus, E.I.T.
Senior Engineering Associate
Engineering Division
Development Services

Final Status

Task End Date Reviewer's Name Type of Review Description
10/23/2006 DELMA ROBEY APPROVAL SHELF Completed
10/23/2006 DELMA ROBEY OUT TO CUSTOMER Completed
10/23/2006 GERARDO BONILLA REJECT SHELF Completed