| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 07/24/2006 | ANDREW CONNOR | NPPO | REVIEW | Approv-Cond | |
| 07/24/2006 | PETER MCLAUGHLIN | ZONING | REVIEW | Denied | Site plan approval required. |
| 08/08/2006 | JASON GREEN | ENGINEERING | REVIEW | Approved | DATE: August 9, 2006 SUBJECT: Fire Station #22 TO: Michael Becherer, WSM Architects LOCATION: 6810 S Alvernon Way, T15S R14E Sec16, Ward 5 REVIEWERS: Jason Green, CFM ACTIVITY: T06BU01756 SUMMARY: Engineering Division of Development Services Department has received and reviewed the submitted grading plan, landscape plan, drainage report, geotechnical report, and Stormwater Pollution Prevention Plan (SWPPP). The drainage report was reviewed for grading plan purpose only. Engineering Division recommends approval of the grading plan with the following condition: 1. Provide a typical sand/oil interceptor at the drainpipe for the hose wash out area. The wash out area must provide for a sand/oil interceptor prior to the runoff entering the sewer system. For any questions call me at 791-5550, extension 1189. Jason Green, CFM Senior Engineer Associate Engineering Division Development Services |