Permit Number: T06BU01725
Parcel: 113071220

Review Status: Completed

Review Details: POOL:COMM-MODEL

Permit Number - T06BU01725
Review Name: POOL:COMM-MODEL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/18/2006 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. The site plan submitted with this project was revised without the knowledge or permission of the registrant and is in violation of ARS 32-125 (D). It is unlawful for any nonregistrant to cause or permit the illegal use of a registrant's seal, signature or stamp on any document prepared by the nonregistrant. Provide a properly sealed site plan.
2. The font size used on the drawings shall be a minimum of 1/8-inch (all upper case). Reference Section 302.3, Uniform Administrative Code, 1997.
3. Provide evidence, including testing by an approved testing agency, to substantiate the claim that the proposed alternative to a manufactured safety release system complies with the intent of ASME A112.19.17 to prevent high vacuum suction entrapments. Reference Section 301.2, UPC 2003.
4. Provide a complete design for the circulation, filtration, water supply, wastewater disposal, and heating of the pool and spa. Reference ANSI/NSPI-1 2003 and ANSI/NSPI-2 1999.
07/18/2006 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Provide a complete design for heating of the pool and spa, including listing information for all equipment. Reference Section 106.3.1, IMC 2003.
2. The font size used on the drawings shall be a minimum of 1/8-inch (all upper case). Reference Section 302.3, Uniform Administrative Code, 1997.
07/26/2006 BOB SUBA ELECTRICAL-COMMERCIAL REVIEW Approved
08/11/2006 RAUL PALMA BUILDING-COMMERCIAL REVIEW Denied 1) Site plan- provide a site plan that is more legible, one
that all notes and dimensions can be read.
2) Specify the accessible route for ADA, dimension gate
clearances, and slope of ramps.
3) Show and specify height of latch on gate, gate shall
be self-closing.
4) How is the soil categorized A',B' ETC. By a soil report?
CLARIFY!
08/28/2006 DAVID RIVERA ZONING REVIEW Denied 08/28/06

Development Services Department
Zoning Review Section

David Rivera
Principal Planner

Comments:

1. The submitted plan for the POOL and structures has been reviewed by Zoning Review Section but cannot approve the plan until it has been approved by the Engineering, and Landscape Review Sections and until all zoning comments or concerns have been addressed.

2. Zoning could not verify that a revised site plan has been approved and stamped. If a revised site plan has been submitted for review and approval with the proposed expansion, please submit two copies of the approved and stamped site, landscape, and NPPO plans.

3. Zoning will re-review the POOL and structures plan on the next submittal to ensure compliance with the approved and stamped revised site plan. Additional comments may be forthcoming.

4. If a revised site plan has not been submitted for review and approval, please refer to development standards 2-02 for site content and design. The site plan must be drawn to comply with the Development Standards 2-02 and standards relevant to pedestrian access, parking, and landscaping, setbacks, etc.