Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T06BU01666
Parcel: 106040310

Address:
431 E YAVAPAI RD

Review Status: Completed

Review Details: GRADING

Permit Number - T06BU01666
Review Name: GRADING
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/07/2006 ANDREW CONNOR NPPO REVIEW Approv-Cond
07/25/2006 JOSE ORTIZ ENGINEERING REVIEW Denied DATE: July 26, 2006
To: AMEC Infrastructure
3295 W. Ina Road
Suite 200
Tucson, Arizona 85741

FROM: Jose E. Ortiz, PE
Engineering Division

SUBJECT: 431 E. Yavapai Rd
Grading Plan T06BU01666 (First Review)
T13S, R13E, Section 25

RESUBMITTAL REQUIRED: Grading Plan

The Grading Plan (GP) cannot be approved as submitted. Please address the following review comments prior to the next submittal.

Grading Plan:

1. Please include a response letter to the comments along with the corrected copies of the GP.
2. Ensure all proposed grading remains on site by showing limits of grading and all gradeable area.
3. Sheet 3: Section C-C appears to be flipped based on the section call out on sheet 2. If needed, please revise.
4. Sheet 3: Callout/cross reference the TYPICAL PARKING DETAIL.
5. Sheet 3: Cross reference the INTEGRATED CURB & SIDEWALK detail into Section A-A.
6. Provide additional proposed spot grades along the curb line adjacent to all parking lots to ensure that nuisance ponding does not occur along the curb line.

Drainage report:
No Comments

If you have any questions, I can be reached at 791-4259x305 or Jose.Ortiz@tucsonaz.gov
Jose E. Ortiz, PE
Civil Engineer
City of Tucson/Development Services Department
201 N. Stone Avenue
P.O. Box 27210
Tucson, Arizona 85726-7210
(520) 791-4259x305 office
08/02/2006 PATRICIA GEHLEN ZONING REVIEW Denied Zoning -
8/2/2006
Zoning will review and approve the grading plans once Engineering has approved the plans and the grading plans match the approved tentative plat.

Final Status

Task End Date Reviewer's Name Type of Review Description
08/09/2006 CINDY AGUILAR OUT TO CUSTOMER Completed
08/09/2006 SUE REEVES REJECT SHELF Completed