Permit Number: T06BU01650
Parcel: 133231880

Review Status: Completed

Review Details: RESUBMITTAL - GRADING

Permit Number - T06BU01650
Review Name: RESUBMITTAL - GRADING
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/07/2007 STEVE SHIELDS ZONING REVIEW Denied DSD TRANSMITTAL

FROM: Steve Shields
Lead Planner

PROJECT: Fry's Fuel Center - Speedway & Pantano
T06BU01650
Grading Plan (2nd Review)

TRANSMITTAL DATE: February 8, 2007

1. The grading plan has been reviewed by Zoning Review Section but cannot approve the plan until it has been approved by the Engineering, and Landscape Review Sections and until all zoning comments or concerns have been addressed.

2. Zoning could not verify that the grading plan was in compliance with the approved site plan. Please submit two copies of the approved and stamped site, landscape, and NPPO plans with the next grading plan submittal.

3. Zoning will re-review the grading plan on the next submittal to insure compliance with the approved and stamped site plan. Additional comments may be forthcoming.

If you have any questions about this transmittal, please contact me at Steve.Shields@tucsonaz.gov or (520) 791-5608 ext. 1180.

C:\planning\grading\t06bu01650-2nd

RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Approved site plans and additional requested documents
02/26/2007 ANDREW CONNOR NPPO REVIEW Denied Site plan approval is necessary to continue review.
03/19/2007 PAUL MACHADO ENGINEERING REVIEW Denied To: Tait and Associates DATE: March 20, 2007
Architects
2266 S. Dobson Rd. Ste. 208
Mesa, Arizona 85202

SUBJECT: Fry's Fueling Station, 7770 E. Speedway Blvd.
Site plan T06CM003790, Grading plan T06BU01650 (Third Review)
T14S, R15E, Section 08

RESUBMITTAL REQUIRED: Site Plan, Grading Plan and Drainage Statement.

The Site Plan (SP), Grading Plan (GP) and Drainage Statement (DS) cannot be approved as submitted. Please address the following review comments prior to the next submittal.

Site Plan, Grading Plan:

1. Please include a response letter to the comments along with the corrected copies of the SP, GP and DS.
2. The SP and GP cannot be approved prior to the site plan (T06CM03381) that is currently under review.
3. As per the Federal ADA requirements, all wheel chair ramps shall have the truncated domes instead of the standard grooves that are shown on COT SD 207. Aside from the Truncated Domes, all wheel chair ramps shall be constructed in accordance with COT SD 207. Call out a COT standard detail or show a detail of the H/C ramp on the plans. The truncated domes shall be shown where the sidewalk or ramp meets the P.A.A.L or driveway. This warns the pedestrian that they are about to enter an area with vehicular traffic.
4. Please list estimated cut & fill quantities per D.S. 2-02.2.1.17. There seems to be a discrepancy with the amounts of cut and fill between the Site plan and Grading plan. Revise as required.
6. Submit 4 copies of the grading plan upon re-submittal.
Drainage Statement:
1. The DS has been accepted by engineering.
If you have any questions, I can be reached at 791-5550 x1193 or Paul.Machado@tucsonaz.gov
Paul P. Machado
Senior Engineering Associate
City of Tucson/Development Services Department
201 N. Stone Avenue
P.O. Box 27210
Tucson, Arizona 85726-7210
(520) 791-5550 x1193 office
(520) 879-8010 fax,
C:/7770 E. Speedway Blvd. Site&Grad 3

Final Status

Task End Date Reviewer's Name Type of Review Description
03/30/2007 DELMA ROBEY OUT TO CUSTOMER Completed
03/30/2007 SUE REEVES REJECT SHELF Completed