Permit Number: T06BU01328
Parcel: 132130570

Address:
1051 E BENSON HY

Review Status: Completed

Review Details: RESUBMITTAL - GRADING ALL

Permit Number - T06BU01328
Review Name: RESUBMITTAL - GRADING ALL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/27/2006 JASON GREEN ENGINEERING REVIEW Approved DATE: October 27, 2006
SUBJECT: A Lotta Storage- Grading Plan Engineering review 2nd Submittal
TO: Patricia Gehlen, CDRC Manager
LOCATION: 1051 E Benson Highway, T14S R14E Sec30, Ward 5
REVIEWERS: Jason Green, CFM
ACTIVITY: T06BU01328


SUMMARY: Engineering Division of Development Services Department has received and reviewed the grading plan, drainage report, and the Stormwater Pollution Prevention Plan (SWPPP), and recommend approval of the grading plan at this time.


ยท CGP Part IV.J.2: The operator will post a sign at the main entrance to the site containing: AZPDES authorization number, construction site contact name and telephone number, brief description, location of SWPPP.


GENERAL COMMENTS:


For any questions call me at 791-5550, extension 1189.

Jason Green, CFM
Senior Engineer Associate
Engineering Division
Development Services
10/27/2006 DAVID RIVERA ZONING REVIEW Approved
11/01/2006 ANDREW CONNOR NPPO REVIEW Denied Submit a copy of the approved landscape and native plant preservation plans for reference. The grading application will be reviewed for compliance only when the approved documents are included in the submittal.

Final Status

Task End Date Reviewer's Name Type of Review Description
11/13/2006 CINDY AGUILAR OUT TO CUSTOMER Completed
11/13/2006 CINDY AGUILAR REJECT SHELF Completed