Permit Number: T06BU01155
Parcel: 105097340

Review Status: Completed

Review Details: GRADING

Permit Number - T06BU01155
Review Name: GRADING
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/17/2006 ANDREW CONNOR NPPO REVIEW Denied Submit a copy of the stamped approved development plans including, landscape and native plant preservation plans for reference. The grading application will be reviewed for compliance with the approved documents and applicable codes and standards only when the approved documents are included in the submittal.
05/18/2006 DAVID RIVERA ZONING REVIEW Denied 05/18/06

Development Services Department
Zoning Review Section

David Rivera
Principal Planner

Comments:

1. The grading plan has been reviewed by Zoning Review Section but cannot approve the plan until it has been approved by the Engineering, and Landscape Review Sections and until all zoning comments or concerns have been addressed.

2. Zoning could not verify that the grading plan was in compliance with the approved development plan. Please submit two copies of the approved and stamped development, landscape, and NPPO plans with the next grading plan submittal.

3. Zoning will re-review the grading plan on the next submittal to ensure compliance with the approved site/development plan. Additional comments may be forthcoming.

4. A site card with DSD approvals by Fire, Zoning, Handi-cap, Engineering, and Landscape/NPPO including the approved development plan stamped for site plan approval and signatures is required before the grading plan can be approved by Zoning. Two copies of the approved development plan, landscape and NPPO plans are to be submitted with the grading plans packet for processing and approval as a site plan. No fees are involved in re-stamping the development/tentative plat plans as an approved site plan. The development plan may be walked through for stamps and site card sign off. Submit the following: two copies of the stamped development plan, landscape and NPPO plans must be included with the grading plans packet processed together for site approval.
06/15/2006 LOREN MAKUS ENGINEERING REVIEW Denied DATE: June 22, 2006
TO: Thomas Lodge, MMLA PSOMAS
SUBJECT: Miramonte Commercial, Grading Plan Review
REVIEWER: Loren Makus
ACTIVITY NUMBER: T06BU01155

SUMMARY: The Grading Plan was reviewed by Development Services Department Engineering Division. The Grading Plan was not approved at this time.

Grading Plan Comments:

1. Revise the dumpster detail (E on sheet 2) to provide post barricades along the sides of the enclosure. Provide 10 feet clear between the posts on opposite sides of the enclosure. (DS 6-01.4.2.C)
2. Clearly delineate the grading limits for the project.
3. Clarify in the details or in the plan view how the discharge to the Northmanor Wash will not cause erosion of the bank and bed of the channel.
4. Revise the grading plan to provide the class 2 bicycle parking in the landscaped area to the south of the existing paved walking path as shown on the Development Plan.
5. Provide a representative section for the area north and west of the proposed building. Include the area of adjacent right of way that will be graded. Provide a note indicating that a right-of-way permit will be required for all work in the right-of-way.
6. Show the bike rack south of the pedestrian path as shown on the development plan. Provide details for the pad including dimensions.
7. Clarify the extent of development in the area south of the pedestrian path. It appears from the plans that this area will remain unchanged except for the bike rack and some enhanced landscaping. Provide notes or details on the plan.

Stormwater Pollution Prevention Plan Comments:

8. Update the Stormwater Pollution Prevention Plan to address the specifics of the current project. Include an updated or supplemental site map. Update all of the scheduling and BMP sections as necessary. Please provide a list of changes for effective review.
Revise the Grading Plan to address all of these comments and resubmit four copies of the grading plan and three copies of the SWPPP. If you would like to meet with me to discuss any of these comments please call me at (520) 791-5550 ext. 1161 or email me at loren.makus@tucsonaz.gov.

Loren Makus, E.I.T.
Senior Engineering Associate
Engineering Division
Development Services

Final Status

Task End Date Reviewer's Name Type of Review Description
06/23/2006 CINDY AGUILAR OUT TO CUSTOMER Completed