Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T06BU01139
Parcel: 12510003F

Review Status: Completed

Review Details: GRADING

Permit Number - T06BU01139
Review Name: GRADING
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/15/2006 ANDREW CONNOR NPPO REVIEW Denied Submit a copy of the approved development plans including the landscape and native plant preservation plans for reference. The grading application will be reviewed for compliance with the approved documents and applicable codes and standards only when the approved documents are included in the submittal.
06/05/2006 JOSE ORTIZ ENGINEERING REVIEW Denied To: MMLA Psomas DATE: June 1, 2006
800 E Wetmore Rd FROM: Jose E. Ortiz, PE
Tucson, Arizona 85719 Engineering Division


SUBJECT: Office Depot - El Con Mall
Grading Plan T06BU01139 (First Review)
T14S, R14E, Section 09

RESUBMITTAL REQUIRED: Grading Plan, Drainage Report and SWPPP

The Grading Plan (GP) and Storm Water Pollution Prevention Plan (SWPPP) cannot be approved as submitted. Please address the following review comments prior to the next submittal.

Grading Plan:

1. Please include a response letter to the comments along with the corrected copies of the GP.
2. List subdivision or Development number.
3. Show boundaries of all surface materials (2" versus 4"). Consider hatching these areas for clarity.
4. A permit will be necessary for any work performed within the Right-of-way (i.e. new sidewalks). Contact Permits and Codes at (520) 791-5100 for permit information.
5. Consider using stabilization material along the proposed earth channel to prevent undesired erosion along the banks of the channel.
6. The grading plan needs to be a stand alone construction document for all civil work; therefore keynote 2 and keynote 8 (referring to the loading zone) will need to be cross referenced with a detail within the grading plans.
7. On the Horizontal control sheet please provide additional dimensions to tie down the location of the catch basin in the loading zone and additional dimensions of the sidewalk along Broadway.
8. The comments for this submittal are minimal; therefore Engineering will permit the next submittal to come through as a walk through review.


Drainage report:
1. No Comments

Storm Water Pollution Prevention Plan:
1. No Comments, Attached is a green form "AZPDES -Posting Requirements". This document needs to be posted at the construction site; therefore make this form available to the contractor and inform them that this needs to be filled prior to any grading of the site. The contractor should consider having this formed prepared for the Pre-Con meeting.

If you have any questions, I can be reached at 791-5550 x1191 or Jose.Ortiz@tucsonaz.gov
Jose E. Ortiz, PE
Civil Engineer
City of Tucson/Development Services Department
201 N. Stone Avenue
P.O. Box 27210
Tucson, Arizona 85726-7210
(520) 791-5550 x1191 office
(520) 879-8010 fax
06/11/2006 DAVID RIVERA ZONING REVIEW Denied 06/11/06

Development Services Department
Zoning Review Section

David Rivera
Principal Planner

Comments:

1. The grading plan has been reviewed by Zoning Review Section but cannot approve the plan until it has been approved by the Engineering, and Landscape Review Sections and until all zoning comments or concerns have been addressed.

2. Zoning could not verify that the grading plan was in compliance with the approved development plan. Please submit two copies of the approved and stamped development, landscape, and NPPO plans with the next grading plan submittal.

3. Zoning will re-review the grading plan on the next submittal to ensure compliance with the approved site/development plan. Additional comments may be forthcoming.

4. A site card with DSD approvals by Fire, Zoning, Handi-cap, Engineering, and Landscape/NPPO including the approved development plan stamped for site plan approval and signatures is required before the grading plan can be approved by Zoning. Two copies of the approved development plan, landscape and NPPO plans are to be submitted with the grading plans packet for processing and approval as a site plan. No fees are involved in re-stamping the development/tentative plat plans as an approved site plan. The development plan may be walked through for stamps and site card sign off. Submit the following: two copies of the stamped development plan, landscape and NPPO plans must be included with the grading plans packet processed together for site approval.

Final Status

Task End Date Reviewer's Name Type of Review Description
06/15/2006 DELMA ROBEY OUT TO CUSTOMER Completed
06/15/2006 SUE REEVES REJECT SHELF Completed