05/26/2006 CHRISTY FOREMAN BUILDING-COMMERCIAL REVIEW Denied CITY OF TUCSON DEVELOPMENT SERVICES
STRUCTURAL REVIEW COMMENTS

DATE: 5/31/06
ACTIVITY NUMBER:
PROJECT NAME: Retaining walls - Liberty Village
PROJECT ADDRESS:
ARCHITECT / ENGINEER: Moizuddin Ahmed
PROJECT REVIEWER: Christy Foreman


TRANSMIT ORIGINAL DRAWINGS WITH NEXT SUBMITTAL.

PLEASE CALL AT 791-5550 X1108 OR EMAIL AT CFOREMA1@TUCSONAZ.GOV IF YOU CARE TO DISCUSS.

1) Provide site plan with grades shown on each end and side of wall to verify how much soil is to be retained.
2) Engineer needs to seal / stamp site plan showing location of retaining wall.
3) Per page 13 of soils report specify on details drain rock layer shall be at least one foot wide and extend up the wall to within 2 ft. of the ground surface.
4) Specifications on page 2 Bar 'D' specifies #4 @ 18" o.c. and detail and specifications on page 17 specifies #5 @ 16" o.c. please clarify which specification is correct.