Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: WALLS SUBMITTAL
Permit Number - T06BU01030
Review Name: WALLS SUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 05/24/2006 | KEN VAN KARSEN | BUILDING-RESIDENTIAL | REVIEW | Passed | |
| 05/31/2006 | CHRISTY FOREMAN | BUILDING-COMMERCIAL | REVIEW | Denied | CITY OF TUCSON DEVELOPMENT SERVICES STRUCTURAL REVIEW COMMENTS DATE: 5/31/06 ACTIVITY NUMBER: PROJECT NAME: Retaining walls - Liberty Village PROJECT ADDRESS: ARCHITECT / ENGINEER: Moizuddin Ahmed PROJECT REVIEWER: Christy Foreman TRANSMIT ORIGINAL DRAWINGS WITH NEXT SUBMITTAL. PLEASE CALL AT 791-5550 X1108 OR EMAIL AT CFOREMA1@TUCSONAZ.GOV IF YOU CARE TO DISCUSS. 1) Provide site plan with grades shown on each end and side of wall to verify how much soil is to be retained. 2) Engineer needs to seal / stamp site plan showing location of retaining wall. 3) Per page 13 of soils report specify on details drain rock layer shall be at least one foot wide and extend up the wall to within 2 ft. of the ground surface. 4) Specifications on page 2 Bar 'D' specifies #4 @ 18" o.c. and detail and specifications on page 17 specifies #5 @ 16" o.c. please clarify which specification is correct. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 06/15/2006 | SUE REEVES | OUT TO CUSTOMER | Completed |
| 06/15/2006 | SUE REEVES | REJECT SHELF | Completed |