Permit Number: T06BU00987
Parcel: 105123390

Address:
4133 N STONE AV

Review Status: Completed

Review Details: POOL:COMM-MODEL

Permit Number - T06BU00987
Review Name: POOL:COMM-MODEL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/06/2006 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied Revise the size of the gas line from the meter to the pool and spa heaters per Section 1217, UPC 2003.
11/06/2006 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Provide plans, drawn to scale. Note that some of the drawings show the pool as a mirror image of the pool shown on other drawings; which version is correct? Reference Section 302.2, Uniform Administrative Code, 1997.
2. Show location and size (on the drawings) of the submitted alternative means of providing vacuum release at a suction outlet caused by a blockage of the suction outlet. Reference ASME A112.19.17-2002, "Manufactured Safety Vacuum Release Systems (SVRS) for Residential and Commercial Swimming Pool, Spa, Hot Tub, and Wading Pool Suction Systems".
11/28/2006 CHRISTY FOREMAN BUILDING-COMMERCIAL REVIEW Denied 1) ENGINEER OF RECORD MUST SEAL AND SIGN ALL PLAN PAGES THAT REFERENCE POOL LAYOUT.
2) CLARIFY (DETAIL) HOW YOU'VE MET ANSI/NSPI-1 SECTION 6.3.2 REQUIREMENTS FOR FLOOR SLOPE. SEE POOL SECTION DRAWING.
3) CLARIFY CONTROL JOINTS PER ANSI/NSPI-1 SECTION 7.1.11. IT APPEARS THIS DETAIL IS NOT A PART OF THE APPROVED MODEL PLAN.

4) PER SPECIFICATIONS ON STRUCTURAL SHT. PLEASE LOCATE THE FOLLOWING ITEMS ON DRAWING SHOWING POOL LAYOUT. CLARIFY COMPLIANCE WITH ANSI/NSPI-1 SECTIONS 18.1 FOR HAND HOLDS; 18.2 ROPE AND FLOAT LINE; 18.3.1.2, 18.3.7 VERTICAL DEPTH MARKERS; 18.3.9 "NO DIVING" SYMBOLS; 18.5.1 LIFE SAVING EQUIPMENT; AND 18.5.2 TELEPHONE LOCATION.
5) CLARIFY COMPLIANCE WITH SECTION 23.5 OF ANSI/NSPI-1 POOL LADDER DESIGN AND CONSTRUCTION.
6) PROVIDE CLARIFICATION / SPECIFICATION OF HANDRAILS FOR STAIRS PER SECTION 23.4 OF ANSI/NSPI-1.