Permit Review Detail
Review Status: Completed
Review Details: POOL:COMM-MODEL
Permit Number - T06BU00987
Review Name: POOL:COMM-MODEL
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
11/06/2006 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | Revise the size of the gas line from the meter to the pool and spa heaters per Section 1217, UPC 2003. |
11/06/2006 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Provide plans, drawn to scale. Note that some of the drawings show the pool as a mirror image of the pool shown on other drawings; which version is correct? Reference Section 302.2, Uniform Administrative Code, 1997. 2. Show location and size (on the drawings) of the submitted alternative means of providing vacuum release at a suction outlet caused by a blockage of the suction outlet. Reference ASME A112.19.17-2002, "Manufactured Safety Vacuum Release Systems (SVRS) for Residential and Commercial Swimming Pool, Spa, Hot Tub, and Wading Pool Suction Systems". |
11/28/2006 | CHRISTY FOREMAN | BUILDING-COMMERCIAL | REVIEW | Denied | 1) ENGINEER OF RECORD MUST SEAL AND SIGN ALL PLAN PAGES THAT REFERENCE POOL LAYOUT. 2) CLARIFY (DETAIL) HOW YOU'VE MET ANSI/NSPI-1 SECTION 6.3.2 REQUIREMENTS FOR FLOOR SLOPE. SEE POOL SECTION DRAWING. 3) CLARIFY CONTROL JOINTS PER ANSI/NSPI-1 SECTION 7.1.11. IT APPEARS THIS DETAIL IS NOT A PART OF THE APPROVED MODEL PLAN. 4) PER SPECIFICATIONS ON STRUCTURAL SHT. PLEASE LOCATE THE FOLLOWING ITEMS ON DRAWING SHOWING POOL LAYOUT. CLARIFY COMPLIANCE WITH ANSI/NSPI-1 SECTIONS 18.1 FOR HAND HOLDS; 18.2 ROPE AND FLOAT LINE; 18.3.1.2, 18.3.7 VERTICAL DEPTH MARKERS; 18.3.9 "NO DIVING" SYMBOLS; 18.5.1 LIFE SAVING EQUIPMENT; AND 18.5.2 TELEPHONE LOCATION. 5) CLARIFY COMPLIANCE WITH SECTION 23.5 OF ANSI/NSPI-1 POOL LADDER DESIGN AND CONSTRUCTION. 6) PROVIDE CLARIFICATION / SPECIFICATION OF HANDRAILS FOR STAIRS PER SECTION 23.4 OF ANSI/NSPI-1. |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
12/12/2006 | GERARDO BONILLA | OUT TO CUSTOMER | Completed |
12/12/2006 | SUE REEVES | REJECT SHELF | Completed |