Permit Review Detail
Review Status: Completed
Review Details: POOL:COMM-MODEL
Permit Number - T06BU00987
Review Name: POOL:COMM-MODEL
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
06/30/2006 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | The submitted drawings do not provide enough information to demonstrate compliance with the requirements of ANSI/NSPI-1 2003 for a Class C pool and ANSI/NSPI-2 1999 for a public spa. |
06/30/2006 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | The submitted drawings do not provide enough information to demonstrate compliance with the requirements of ANSI/NSPI-1 2003 for a Class C pool and ANSI/NSPI-2 1999 for a public spa. |
07/07/2006 | BOB SUBA | ELECTRICAL-COMMERCIAL | REVIEW | Denied | 1.Provide proper sized font (1/8th" min.) 2.See attatched plan review electrical requirements(see highlighted items& include existing loads with this pool loads). |
07/26/2006 | AOLIVO1 | ZONING | REVIEW | Needs Review | |
07/26/2006 | AOLIVO1 | BUILDING-COMMERCIAL | REVIEW | Needs Review |