Permit Number: T06BU00987
Parcel: 105123390

Address:
4133 N STONE AV

Review Status: Completed

Review Details: POOL:COMM-MODEL

Permit Number - T06BU00987
Review Name: POOL:COMM-MODEL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/15/2006 CHRISTY FOREMAN BUILDING-COMMERCIAL REVIEW Denied CITY OF TUCSON DEVELOPMENT SERVICES
STRUCTURAL REVIEW COMMENTS

DATE: 5/18/06
ACTIVITY NUMBER: T06BU00987 N. Stone
PROJECT ADDRESS: Semi-public pool Stone Curves
ARCHITECT / ENGINEER: Ammtec Consulting, Inc.
PROJECT REVIEWER: Christy Foreman


TRANSMIT ORIGINAL DRAWINGS WITH NEXT SUBMITTAL.

PLEASE CALL AT 791-5550 X1108 OR EMAIL AT CFOREMA1@CI.TUCSON.AZ.US IF YOU CARE TO DISCUSS.


1) Class C pool requires a minimum of 4ft deck width around pool per ANSI / NSP1-1 section 5.5.6.3. Dimension drawings.
2) Specify slope of deck per 5.1.7.
3) ANSI / NSP1-1 section 5.2 Entry / Exit: All pools shall have at least two. Please specify on drawings.
4) Specify / detail stairs and handrails per ANSI / NSP1-1 section 5.3.
5) Specify pool enclosure per City of Tucson Amendments section AG105.
6) Class C pools require lifeguard chair for pool area over 1800 sq. ft according to section 16.3 ANSI / NSP1-1.
7) Provide depth markers according to section 16.3 ANSI / NSP1-1.
8) Clarify maximum user load according to section 4.9 ANSI / NSP1-1.
9) Water depths specified per section 4.4 ANSI / NSP1-1.
05/18/2006 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied Provide sealed drawings that show compliance with the requirements of ANSI/NSPI-1 2003 for a Class C pool and ANSI/NSPI-2 1999 for a public spa.
05/18/2006 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Provide sealed drawings that show compliance with the requirements of ANSI/NSPI-1 2003 for a Class C pool and ANSI/NSPI-2 1999 for a public spa.
05/19/2006 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied TRANSMIT ORIGINAL DRAWINGS WITH NEXT SUBMITTAL.

PLEASE CALL AT 791-5550 X1106 OR EMAIL AT Linda.Buczynski@tucsonaz.gov
IF YOU CARE TO DISCUSS.

PROVIDE SEALED DRAWINGS THAT SHOW COMPLIANCE WITH NEC 2002, THE 2003 IECC, AND THE TUCSON LIGHTING CODE.

Final Status

Task End Date Reviewer's Name Type of Review Description
05/22/2006 GBONILL1 OUT TO CUSTOMER Completed
05/22/2006 SUE REEVES REJECT SHELF Completed