Permit Review Detail
Review Status: Completed
Review Details: POOL:COMM-MODEL
Permit Number - T06BU00987
Review Name: POOL:COMM-MODEL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 05/15/2006 | CHRISTY FOREMAN | BUILDING-COMMERCIAL | REVIEW | Denied | CITY OF TUCSON DEVELOPMENT SERVICES STRUCTURAL REVIEW COMMENTS DATE: 5/18/06 ACTIVITY NUMBER: T06BU00987 N. Stone PROJECT ADDRESS: Semi-public pool Stone Curves ARCHITECT / ENGINEER: Ammtec Consulting, Inc. PROJECT REVIEWER: Christy Foreman TRANSMIT ORIGINAL DRAWINGS WITH NEXT SUBMITTAL. PLEASE CALL AT 791-5550 X1108 OR EMAIL AT CFOREMA1@CI.TUCSON.AZ.US IF YOU CARE TO DISCUSS. 1) Class C pool requires a minimum of 4ft deck width around pool per ANSI / NSP1-1 section 5.5.6.3. Dimension drawings. 2) Specify slope of deck per 5.1.7. 3) ANSI / NSP1-1 section 5.2 Entry / Exit: All pools shall have at least two. Please specify on drawings. 4) Specify / detail stairs and handrails per ANSI / NSP1-1 section 5.3. 5) Specify pool enclosure per City of Tucson Amendments section AG105. 6) Class C pools require lifeguard chair for pool area over 1800 sq. ft according to section 16.3 ANSI / NSP1-1. 7) Provide depth markers according to section 16.3 ANSI / NSP1-1. 8) Clarify maximum user load according to section 4.9 ANSI / NSP1-1. 9) Water depths specified per section 4.4 ANSI / NSP1-1. |
| 05/18/2006 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | Provide sealed drawings that show compliance with the requirements of ANSI/NSPI-1 2003 for a Class C pool and ANSI/NSPI-2 1999 for a public spa. |
| 05/18/2006 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | Provide sealed drawings that show compliance with the requirements of ANSI/NSPI-1 2003 for a Class C pool and ANSI/NSPI-2 1999 for a public spa. |
| 05/19/2006 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | TRANSMIT ORIGINAL DRAWINGS WITH NEXT SUBMITTAL. PLEASE CALL AT 791-5550 X1106 OR EMAIL AT Linda.Buczynski@tucsonaz.gov IF YOU CARE TO DISCUSS. PROVIDE SEALED DRAWINGS THAT SHOW COMPLIANCE WITH NEC 2002, THE 2003 IECC, AND THE TUCSON LIGHTING CODE. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 05/22/2006 | GBONILL1 | OUT TO CUSTOMER | Completed |
| 05/22/2006 | SUE REEVES | REJECT SHELF | Completed |