Permit Number: T06BU00948
Parcel: 133092570

Review Status: Completed

Review Details: WALLS

Permit Number - T06BU00948
Review Name: WALLS
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/06/2006 DOUG LAAKSO BUILDING-COMMERCIAL REVIEW Denied .. T06BU00948 .. 8060 E HAMPTON DRIVE .. RETAINING WALL: 66LF OF 4' .. DGL .. 1ST REVIEW COMMENTS .. 6/6/06 ..

TRANSMIT PRIOR SUBMITTAL/S WITH NEXT SUBMITTAL.

S1. Provide site plan sealed and signed by Engineer of Record for the retaining wall.
S2. Provide adequate spot elevations to show changes in grades for the length of the wall conform to design of retaining wall on site plan.
S3. Dimensionally locate retaining wall from two adjacent property lines on site plan to show where wall is to be located on site.
S4. Provide submittal including structural calculations conforming to 1/8 inch minimum lettering all capitals.
S5. The detail shows a 3.0 feet maximum height of retained earth, site plan shows a 4 foot high retaining wall which is correct?
S6. Clarify weepholes are daylighted on low side of wall to allow the retaining wall drain.
S7. Clarify location of vertical reinforcing in the retaining wall from the face of the wall.



Questions? Call Douglas Laakso Structural Plans Examiner for the City of Tucson Development Services Department at (520) 791-5550 x1111, email at <Doug.Laakso@tucsonaz.gov.> or visit City of Tucson , DSD website : www.tucsonaz.gov/dsd.

Final Status

Task End Date Reviewer's Name Type of Review Description
06/07/2006 DELMA ROBEY REJECT SHELF Completed