Permit Number: T06BU00943
Parcel: 10309078A

Review Status: Completed

Review Details: COMMERCIAL-BLDG/FIRE/ZONING/ENG

Permit Number - T06BU00943
Review Name: COMMERCIAL-BLDG/FIRE/ZONING/ENG
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/05/2006 MARTIN BROWN FIRE REVIEW Approved
06/08/2006 RAUL PALMA BUILDING-COMMERCIAL REVIEW Denied 1) The value for Kz is 1.45 for exp. C as per table
1609.6.2.1(4) Correct the calcs affected by this
change.
06/11/2006 DAVID RIVERA ZONING REVIEW Denied 06/11/06

Development Services Department
Zoning Review Section

David Rivera
Principal Planner

Comments:

1. Zoning has reviewed the building plans but cannot approve them at this time until the plans have been completely approved through the commercial review process.

2. The required building setback for the proposed structure adjacent to R-1 Zoning is based on one and one-half times the height of the structure as measured from design grade. The overall height of the structure appears to be 34'-8". The required building setback is 52 feet. Revise the site plan to indicate that the structure will be setback 52 feet from the west property line.

Final Status

Task End Date Reviewer's Name Type of Review Description
06/16/2006 DELMA ROBEY OUT TO CUSTOMER Completed
06/16/2006 SUE REEVES REJECT SHELF Completed