Permit Number: T06BU00814
Parcel: 141353620

Review Status: Completed

Review Details: POOL/SPA

Permit Number - T06BU00814
Review Name: POOL/SPA
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/18/2006 DAVE MANN FIRE REVIEW Approved
08/21/2006 RAUL PALMA BUILDING-COMMERCIAL REVIEW Denied 1) Show location of fence, gate, and specify the width of
the gate as per ADA. Section 404.
2) Show accessiblity path to pool from building REC
center.
3) Show location of ADA bathrooms.
4) Any change in elevation greater than 1/2" in height
shall be ramped.
5) Refer to pool details; the longitudinal cross-section re-
fers to cross-section A-A, where is it on plans?

Final Status

Task End Date Reviewer's Name Type of Review Description
08/25/2006 DELMA ROBEY OUT TO CUSTOMER Completed
08/25/2006 SUE REEVES REJECT SHELF Completed