Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T06BU00813
Parcel: Unknown

Address:
2981 E ALLEN RD

Review Status: Completed

Review Details: POOL/SPA

Permit Number - T06BU00813
Review Name: POOL/SPA
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/09/2006 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Show the proposed location of water disposal for pool drainage.
2. Clarify the means of adding makeup water to the pool. The hose bibb is shown on the drawing with a waterline running from the location of the hose bibb out to an auto fill valve symbol on the deck and the equipment listing calls out a Watts 008QT vacuum breaker as an "auto fill".
3. Coordinate the pipe sizes shown on the underground piping schedule with the pipe sizes shown on the pool plumbing schematic.
4. Second request. Show how the pool provides a safety vacuum release system.
06/22/2006 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied TRANSMIT ORIGINAL DRAWINGS WITH NEXT SUBMITTAL.

PLEASE CALL AT 791-5550 X1106 OR EMAIL AT Linda.Buczynski@tucsonaz.gov
IF YOU CARE TO DISCUSS.

1. Clarify the location of the pool light on the sealed plans.
2. Provide a fixture cut sheet for the pool light.
3. Demonstrate compliance with the Tucson Lighting Code.
4. Provide specifications for the pool bonding. Reference NEC 680.26.
5. Plans shall clearly demonstrate compliance with NEC 680.11 drainage requirements.
07/21/2006 DOUG LAAKSO BUILDING-COMMERCIAL REVIEW Denied .. T06BU00813.. 2981 EAST ALLEN ROAD .. SEMI-PUBLIC SWIMMING POOL .. DGL .. 2ND REVIEW .. 7/21/06 ..

TRANSMIT PRIOR SUBMITTAL/S WITH NEXT SUBMITTAL.

S1. See prior comment #S2. (S2. Provide fully completed Code Review Checklist, by Architect or Engineer of Record. )
S2. See prior comment # S8. ( S8. Provide Inspection Program by Registrant of Record per 1997 U A C Section 302.5.)
S3. See prior comment #S10,show location and letter size of address at street and at pool. (S10. Provide an Official Address Slip from Pima County Addressing, for changing the address from an administrative address to the Official Address, for this lot/location/common area. Provide address on site per Pima County Addressing Ordinance and per IBC Section 501.2.)
S4. Provide sealed drawings detailing on drawings how the pool and pool area complies with ANSI/NSPI-1 1991 per 2003 IBC Commentary , including Dimensional Design, Decks and Deck Equipment, Specific Safety Features, and explain Pool Class on drawings.

Questions? Call Douglas Laakso Structural Plans Examiner for the City of Tucson Development Services Department at (520) 791-5550 x1111, email at <Doug.Laakso@tucsonaz.gov.> or visit City of Tucson , DSD website : www.tucsonaz.gov/dsd.

Final Status

Task End Date Reviewer's Name Type of Review Description
07/27/2006 SUE REEVES OUT TO CUSTOMER Completed
07/27/2006 SUE REEVES REJECT SHELF Completed