Permit Review Detail
Review Status: Completed
Review Details: POOL/SPA
Permit Number - T06BU00813
Review Name: POOL/SPA
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 04/17/2006 | MARTIN BROWN | FIRE | REVIEW | Approved | |
| 05/02/2006 | DOUG LAAKSO | BUILDING-COMMERCIAL | REVIEW | Denied | .. T06BU00813 .. 2981 EAST ALLEN ROAD .. SEMI-PUBLIC SWIMMING POOL .. DGL .. 1ST REVIEW .. 5/03/06 .. TRANSMIT PRIOR SUBMITTAL/S WITH NEXT SUBMITTAL. S1. Who is the Arizona Registrant (Architect or Engineer) of Record for this Project? S2. Provide fully completed Code Review Checklist, by Architect or Engineer of Record. S3. Provide Registrant's sealed and signed drawings for this Project. S4. Provide Site Plan sealed and signed by Registrant of Record. S5. Follow Arizona State Board of Technical Registration Rules and Regulations regarding use/ modification of another Registrant's Plans. S6. Revise the font size used on the drawings and calculations to a minimum of 1/8 inch (all upper case). Reference Section 302.3, Uniform Administrative Code, 1997. S7. Provide readable drawings Patio Pools and AmmTec Consulting ,Inc drawings are much to light to read or for Record purposes. S8. Provide Inspection Program by Registrant of Record per 1997 U A C Section 302.5. S9. Special Inspection required for retaining walls per 1997 Uniform Administrative Code Section 301, 302.5, 306, ref: details y and u, Negative edge detail and Freestanding wall detail. S10. Provide an Official Address Slip from Pima County Addressing, for changing the address from an administrative address to the Official Address, for this lot/location/common area. Provide address on site per Pima County Addressing Ordinance and per IBC Section 501.2. S11. This review can not be completed because of the condition of the Submittal. Provide a complete, readable and properly documented Submittal and the review can go forward. Additional comments may be forthcoming with future Submittals. Questions? Call Douglas Laakso Structural Plans Examiner for the City of Tucson Development Services Department at (520) 791-5550 x1111, email at <Doug.Laakso@tucsonaz.gov.> or visit City of Tucson , DSD website : www.tucsonaz.gov/dsd. |
| 05/05/2006 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Revise the font size used on the drawings to a minimum of 1/8-inch (all upper case). Reference Section 302.3, Uniform Administrative Code, 1997. 2. Show the proposed location of filter backwash or pool draining water disposal. 3. Show the means of adding makeup water to the pool. 4. Show that the proposed pump is capable of providing the proposed filter flow rate against the total dynamic head of the filter system. 5. Show how the pool provides a safety vacuum release system. |
| 05/09/2006 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | .. T06BU00813 .. 2981 EAST ALLEN ROAD .. SEMI-PUBLIC SWIMMING POOL .. LAB .. 1ST REVIEW .. 5/09/06 .. TRANSMIT PRIOR SUBMITTAL/S WITH NEXT SUBMITTAL. T06BU00813 .. 2981 EAST ALLEN ROAD .. SEMI-PUBLIC SWIMMING POOL .. LAB .. 1ST REVIEW .. 5/09/06 .. TRANSMIT PRIOR SUBMITTAL/S WITH NEXT SUBMITTAL. 1. Based upon the presentation of the plans and in accordance with the State Board of Technical Registration Rules, this plan should be designed and sealed by an Arizona registered professional Electrical Engineer. 2. Electrical design shall comply with NEC 2002, not IRC. 3. Provide Registrant's sealed and signed drawings for this Project. 4. Revise the font size used on the drawings and calculations to a minimum of 1/8 inch (all upper case). Reference Section 302.3, Uniform Administrative Code, 1997. 5. Site shall comply with the requirements of the Tucson Lighting /code. Questions? Call Linda Buczynski Electrical Plans Examiner for the City of Tucson Development Services Department at (520) 791-5550 x1106, email at <Linda.Buczynski@tucsonaz.gov.> or visit City of Tucson , DSD website : www.tucsonaz.gov/dsd. |
| 05/10/2006 | RSHERRY1 | WWM | REVIEW | Passed |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 05/12/2006 | AMERY KLAPPERT | OUT TO CUSTOMER | Completed |
| 05/12/2006 | SUE REEVES | REJECT SHELF | Completed |