Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T06BU00781
Parcel: 140553290

Review Status: Active

Review Details: RESUBMITTAL

Permit Number - T06BU00781
Review Name: RESUBMITTAL
Review Status: Active
Review Date Reviewer's Name Type of Review Description Status Comments
05/23/2006 CHRISTY FOREMAN BUILDING-COMMERCIAL REVIEW Denied CITY OF TUCSON DEVELOPMENT SERVICES
STRUCTURAL REVIEW COMMENTS

DATE: 5/26/06
ACTIVITY NUMBER:
PROJECT NAME: Retaining wall with patio wall on top.
PROJECT ADDRESS: Corozon Del Pueblo
ARCHITECT / ENGINEER: LSI Group
PROJECT REVIEWER: CHRISTY FOREMAN


TRANSMIT ORIGINAL DRAWINGS WITH NEXT SUBMITTAL.

PLEASE CALL AT 791-5550 X1108 OR EMAIL AT CFOREMA1@TUCSONAZ.GOV IF YOU CARE TO DISCUSS.

1) Site plan for each lot shall have grade elevations noted on each side of wall and at each end.
2) Text size on retaining wall details shall be a minimum of 1/8" hgt. All capitals per City of Tucson submittal requirements.
3) Soil report provided was by GRC Consultants, Inc. Report No: 4739-001 LSI Group specified Report #23586 for the st