05/23/2006 CHRISTY FOREMAN BUILDING-COMMERCIAL REVIEW Denied CITY OF TUCSON DEVELOPMENT SERVICES
STRUCTURAL REVIEW COMMENTS

DATE: 5/26/06
ACTIVITY NUMBER:
PROJECT NAME: Retaining wall with patio wall on top.
PROJECT ADDRESS: Corozon Del Pueblo
ARCHITECT / ENGINEER: LSI Group
PROJECT REVIEWER: CHRISTY FOREMAN


TRANSMIT ORIGINAL DRAWINGS WITH NEXT SUBMITTAL.

PLEASE CALL AT 791-5550 X1108 OR EMAIL AT CFOREMA1@TUCSONAZ.GOV IF YOU CARE TO DISCUSS.

1) Site plan for each lot shall have grade elevations noted on each side of wall and at each end.
2) Text size on retaining wall details shall be a minimum of 1/8" hgt. All capitals per City of Tucson submittal requirements.
3) Soil report provided was by GRC Consultants, Inc. Report No: 4739-001 LSI Group specified Report #23586 for the st