Permit Number: T06BU00777
Parcel: Unknown

Review Status: Completed

Review Details: RESUBMITTAL - GRADING

Permit Number - T06BU00777
Review Name: RESUBMITTAL - GRADING
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/26/2006 ANDREW CONNOR NPPO REVIEW Denied An unpaved planting area, which is a minimum of thirty-four (34) square feet in area and four (4) feet in width, must be provided for each canopy tree per LUC 3.7.2.3. The measurement is always within the planter area and does not include any material which defines the outer edge of the unpaved area" per DS 2-06.3.3.C. Include inside dimensions or planter detail on the grading plans.
07/06/2006 JOSE ORTIZ ENGINEERING REVIEW Denied Gerardo Calza DATE: July 11, 2006
Urban Engineering FROM: Jose E. Ortiz, PE
877 S Alvernon Way Engineering Division
Tucson, Arizona 85711

SUBJECT: Fairview Business Park
Grading Plan T06BU00777 (Second Review)
T13S, R13E, Section 35

RESUBMITTAL REQUIRED: Grading Plan, Drainage Report and SWPPP

The Grading Plan (GP) and Drainage Report (DR) cannot be approved as submitted. Please address the following review comments prior to the next submittal.

Grading Plan:
1. Please include a response letter to the comments along with the corrected copies of the GP.
2. Cross reference sheet numbers of all details to call outs on plan view.
3. Dimension and callout limits of riprap on sheet 6
4. Due to the close proximately of the underground retention basin to Lot 6 ensure that the perforation of stormwater from this system will not create an adverse condition to the proposed overlying slab foundation of Lot 6. This information and be presented in a Geo-Technical report and/or the Drainage Report.

Drainage report:
1. No additional comments

SWPPP:
1. On the SWPPP site map provide additional information in regards to how the new catch basins are going to be protected. Keynote 2 does not appear to apply. Insert modified site map into SWPPPs

If you have any questions, I can be reached at 791-5550 x1191 or Jose.Ortiz@tucsonaz.gov
Jose E. Ortiz, PE
Civil Engineer
City of Tucson/Development Services Department
201 N. Stone Avenue
P.O. Box 27210
Tucson, Arizona 85726-7210
(520) 791-5550 x1191 office
(520) 879-8010 fax
08/17/2006 DAVID RIVERA ZONING REVIEW Denied 08/17/06

Development Services Department
Zoning Review Section

David Rivera
Principal Planner

Comments:

1. The grading plan has been reviewed by Zoning Review Section but cannot approve the plan until it has been approved by the Engineering, and Landscape Review Sections and until all zoning comments or concerns have been addressed.

2. Zoning could not verify that the grading plan was in compliance with the approved tentative plat. Please submit one copy of the CDRC approved and stamped tentative plat, landscape, and NPPO plans with the next grading plan submittal.

3. Zoning will re-review the grading plan on the next submittal to ensure compliance with the CDRC approved and stamped tentative plat. Additional comments may be forthcoming.

4. There areas depicted on the grading plan that do not match the approved tentative plat. Please review all plan sheets and ensure that the design of the development with regards to building area, parking landscaping etc. as approved on the tentative plat/development plan is depicted on the grading plan. Deviations from the tentative plat/development plan will require a resubmittal and approval of the revisions through the CDRC process.

5. Review the details on sheet 3 of the grading plan and revise detail F, M, R, and Q. Some of the details have been annotated with incorrect dimensions and and others with incorrect text.

Final Status

Task End Date Reviewer's Name Type of Review Description
09/06/2006 GERARDO BONILLA OUT TO CUSTOMER Completed
09/06/2006 SUE REEVES REJECT SHELF Completed