Review Details: COMMERCIAL-BLDG/FIRE/ZONING/ENG

Permit Number - T06BU00772
Review Name: COMMERCIAL-BLDG/FIRE/ZONING/ENG
Review Status: Active
Review Date Reviewer's Name Type of Review Description Status Comments
05/24/2006 JASON GREEN ENGINEERING REVIEW Approved DATE: May 24, 2006
SUBJECT: Construction of a Ramada- Engineering Review
ADDRESS: 5935 S Avenida Ribero, Tucson Arizona 85705
PROPERTY OWNER: Tres Pueblos Homeowners Association
LOCATION: T15S R14E Section 08, Tres Pueblos (B60, P001) Common Area C-1
REVIEWER: Jason Green, CFM
ACTIVITY NUMBER: T06BU00772


SUMMARY: The Floodplain Use Permit and site plan were received and reviewed by Engineering Division. The Floodplain Use Permit application, T06OT01330 will be issued for an open sided Ramada. Engineering Division recommends approval of the Floodplain Use Permit.


CONDITIONS OF PERMIT:

The associated improvements are with permit activity number T06OT010330 (Floodplain Use Permit) and T06BU0072 (site plan).

The applicant attests to the fact that the plans and documents submitted represent all of the improvements that will be constructed and are included in the construction plans and/or documents herewith.

This permit is specific to the Ramada construction as shown on this site plan. It shall not apply to any other structure or property, whether attached or unattached, not specified under this permit.

Copies of the site plan/permit documents shall be kept in a readily accessible location on site at all times.

If you have any questions, I can be reached at 791-5550, extension 1189.



Jason Green, CFM
Senior Engineer Associate
Engineering Division
Development Services
06/13/2006 DOUG LAAKSO BUILDING-COMMERCIAL REVIEW Denied .. T06BU00771 .. 5890 SOUTH AVENIDA SELVA DE OCOTE .. TRES PUEBLOS PARK .. DGL .. 1ST REVIEW COMMENTS .. 6/13/06 ..
.. T06BU00772 .. 5935 SOUTH AVENIDA RIBERO .. TRES PUEBLOS PARK .. DGL .. 1ST REVIEW COMMENTS .. 6/13/06 ..


TRANSMIT PRIOR SUBMITTAL/S WITH NEXT SUBMITTAL.

S1. Provide a complete set of drawings for review, this submittal contains drawings R1, R2, R3, R7 of 7 and a drawing for a 12' x 12' ramada.
S2. Provide completed Commercial Plan Submittal Checklist by Architect of Record, including: Signature of Architect/Engineer of Record, Registration number of Registrant of Record, Date form is completed, Job Address and Acknowledge items listed on this Checklist are in this Submittal by checking the adjacent square. See DSD website : www.tucsonaz.gov/dsd, for form.
S3. Provide completed Code Review Checklist, as required by 1997 Uniform Administrative Code Section 302.1, including: Job Address, Architect, Signature, Date, Summary of Governing Regulations, General Building Summary and Allowable Area Calculation. See DSD website : www.tucsonaz.gov/dsd, for form.
S4. Show accessible route on drawings, per International Building Code Section 11 and ANSI A117.1-2003ed :
1. Identify location of accessible route on drawing R1, per IBC Sec 1104 and ANSI Sec 4.
2. Show accessibility to recreational facilities, including basketball court, pet waste station, trash cans, (8'x8' and 12'x12')ramadas, BBQs, picnic tables, benches, Large Play Structure, Small Play Structure, other equipment provided per IBC Sec 1109.14.3.
3. Show location, dimensions and specifications for detectable warnings per IBC Sec 1109.9 and ANSI A117.1 Sec 705.
4. Specifications and location of accessible drinking fountains per IBC Sec 1109.5 and ANSI Sec 602.
5. Ramps, landings, slopes, grade changes and maneuvering clearances.
S5. Submit two sets of shop drawings and calculations, stamped and signed by an Arizona Registered engineer, shop drawings shall be reviewed by and bear the approval of the Engineer or Architect of Record prior to submission to the City of Tucson , Development Services Department for approval prior to erection for the:
1. Pet waste station.
2. Trash cans.
3. (8'x8' and 12'x12')Ramadas.
4. BBQs.
5. Picnic tables.
6. Drinking fountains.
S6. Provide Special Inspection as required by the 1997 Uniform Administrative Code as amended and adopted by the City of Tucson, Section 306:
1. High strength bolting.
2. Shop welding.
S7. Provide addressing per Pima County Addressing Ordinance and IBC section 501.2 on the drawings.
S8. Dimensionally locate the structures on the Site Plan by from two adjacent Property Lines.


Questions? Call Douglas Laakso Structural Plans Examiner for the City of Tucson Development Services Department at (520) 791-5550 x1111, email at <Doug.Laakso@tucsonaz.gov.> or visit City of Tucson , DSD website : www.tucsonaz.gov/dsd.