Permit Number: T06BU00744
Parcel: 11204370H

Review Status: Completed

Review Details: GRADING

Permit Number - T06BU00744
Review Name: GRADING
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/15/2006 PATRICIA GILBERT ENGINEERING REVIEW Denied DATE: April 15, 2006
ACTIVITY NUMBER: T06CM01864 / T06OT00911 / T06BU00744
PROJECT NAME: Lamm Physical Therapy
PROJECT ADDRESS: 3038 East Fort Lowell Road
PROJECT REVIEWER: Patricia Gilbert, Engineering Associate

The following items must be revised or added to the site plan. Please include a response letter with the next submittal that states how all comments have been addressed.

RESUBMITTAL REQUIRED: SITE PLAN, DRAINAGE REPORT, GRADING PLAN


1. A copy of the stamped approved Site Plan must be included with the Grading Plan submittal.

2. The Site Plan is currently in review. Any changes made to the Site Plan must be reflected on the Grading Plan. The Site Plan and Grading Plan must match.

3. Indicate building roof slope, downspouts and sidewalk scuppers. Add note, "All roof spouts will be routed under any adjacent sidewalk." Graphically indicate downspouts and sidewalk scuppers.

4. Add a general note to the plan that the entire property lies within a FEMA floodplain Zone AE. Include the FIRM Panel number. DS 2-02.2.1.A.15.

5. In a general note provide the water surface elevation and include the datum. DS 2-02.2.1.A.15.

6. Indicate the datum used for the finish floor in a general note on the site plan. DS 2-02.2.1.A.15.

7. Provide a general note on the site plan that this development contains a requirement that the applicant, or the applicant's authorized representative, complete a FEMA Elevation Certificate and is returned to the Development Services Department (DSD) Engineering Division prior to approval of final inspection. The original elevation certificate must be returned to the DSD Engineering Division.

8. This project is subject to intersection widening per the MS & R Map. Refer to the diagram located on the lower left hand corner of the MS & R Map found on the following web page, http://www.ci.tucson.az.us/planning/maps/city/msr.pdf. Provide the future ROW dimensions (including the intersection widening) on the site plan, label accordingly.

9. Dimension from street centerline of Fort Lowell Road to the existing and future curb and sidewalk location. DS 2-02.2.1.A.19., 21.

10. Show all easements of record on the site plan. This development has three different lots which would require a cross access, ingress/egress easement for access from Fort Lowell through the two front lots. Revise appropriately. DS 2-02.2.1.A.20.

DRAINAGE REPORT COMMENTS

Provide an addendum to the submitted drainage report with the interpolated water surface elevation, recommended finish floor elevation and the datum used.
04/18/2006 PETER MCLAUGHLIN ZONING REVIEW Denied Site plan approval required prior to grading plan approval.
04/18/2006 PETER MCLAUGHLIN NPPO REVIEW Denied Approved site plan and landscape plan required.

Final Status

Task End Date Reviewer's Name Type of Review Description
09/18/2006 JMORALE1 OUT TO CUSTOMER Completed
09/18/2006 SUE REEVES REJECT SHELF Completed