Review Date Reviewer's Name Type of Review Description Status Comments
06/08/2006 CHRISTY FOREMAN BUILDING-COMMERCIAL REVIEW Denied DATE: 6/8/06
ACTIVITY NUMBER: T06BU00710R
PROJECT NAME: Retaining wall
PROJECT ADDRESS: 4302 E. Ocotillo Desert
ARCHITECT / ENGINEER: Harry J. Lewsley
PROJECT REVIEWER: Christy Foreman


TRANSMIT ORIGINAL DRAWINGS WITH NEXT SUBMITTAL.

PLEASE CALL AT 791-5550 X1108 OR EMAIL AT CFOREMA1@TUCSONAZ.GOV IF YOU CARE TO DISCUSS.

1) Provide Model plan approved by City of Tucson to justify / clarify reinforcing & wall thickness for pool is as specified per structural calculations.
2) Site plan specifies 3 ft. retaining wall. Structural drawings specifies a 5 ft. retaining wall. Please clarify.
3) Provide retaining wall calculations / justification and details stamped by Structural Engineer.
4) Justify there is no surcharge from existing 5 ft. masonry wall on 5 ft. retaining wall.
5) Special Inspection certificate for structural masonry shall be required before the permit will be released.