Permit Review Detail
Review Status: Completed
Review Details: GRADING
Permit Number - T06BU00676
Review Name: GRADING
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 03/29/2006 | PATRICIA GILBERT | ENGINEERING | REVIEW | Denied | DATE: March 29, 2006 ACTIVITY NUMBER: T06BU00676 PROJECT NAME: Carlos Portillo Residence PROJECT ADDRESS: 3518 North Jackson Avenue PROJECT REVIEWER: Patricia Gilbert The following items must be revised or added to the grading plan. Please include a response letter with the next submittal that states how all comments have been addressed. RESUBMITTAL REQUIRED: GRADING PLAN, SITE PLAN, DRAINAGE REPORT, FLOODPLAIN USE PERMIT APPLICATION 1. The Site Plan is currently in review. Any changes made to the Site Plan must be reflected on the Grading Plan. The Site Plan and Grading Plan must match. Once the site plan is approved if all the grading comments below have been addressed the grading plan can be approved. 2. Because this site plan is also being utilized as a grading plan please include the verbiage "Grading Plan" somewhere in the title block. 3. When comparing the contours indicated on the site plan to the contours shown on the Department of Transportation (TDOT) Map site, there is 2' difference. If the contours shown on the site plan are correct there is a differential grading issue. When a plan shows fill in excess of two feet from above existing grade at any location in the outer one hundred feet of the developing site adjacent to residentially zoned property the procedure outlined in Development Standard 11-01.801.A. is required. This process must be complete prior to Grading Plan approval. It is highly recommended to check for accuracy of the contours shown on the site plan. Revise the site/grading plan if necessary. 4. The recommended finish floor elevation (FFE) in the drainage report is 2380.60 Datum NAVD 1988. The FFE noted within the building pad is 2383.00. It is not clear why the FFE noted within the building pad is almost 3' higher then the recommended FFE found in the drainage report. Is it a mistake? Clarify in the response letter and/or revise the site/grading plan. 5. Show roof drainage (flow arrows). DS 2-02.2.1.A.16. 6. In areas where fill is to be used to raise the elevation of the building site, the building line shall be located not less than twenty-five (25) feet landward from any edge of the fill, unless a study prepared by a state-registered professional civil engineer and approved by the city engineer shows that a lesser distance is acceptable. Revise the building pad or submit a study (memo) prepared by a state-registered professional civil engineer. Tucson Code Chapter 26-8.d.2. 7. Indicate on the plan if there are existing or proposed walls on the plan. |
| 04/11/2006 | ANDREW CONNOR | NPPO | REVIEW | Passed | |
| 04/20/2006 | AOLIVO1 | ZONING | REVIEW | Needs Review |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 04/20/2006 | ADRIANNE OLIVO | OUT TO CUSTOMER | Completed |