05/10/2006 CHRISTY FOREMAN BUILDING-COMMERCIAL REVIEW Denied CITY OF TUCSON DEVELOPMENT SERVICES
STRUCTURAL REVIEW COMMENTS

DATE: 5/10/06
ACTIVITY NUMBER: T06BU00666
PROJECT NAME: RETAINING WALL
PROJECT ADDRESS: 127 E. CASTLEFIELD CI
ARCHITECT / ENGINEER: TOM E. RADER
PROJECT REVIEWER: CHRISTY FOREMAN


TRANSMIT ORIGINAL DRAWINGS WITH NEXT SUBMITTAL.

PLEASE CALL AT 791-5550 X1108 OR EMAIL AT CFOREMA1@CI.TUCSON.AZ.US IF YOU CARE TO DISCUSS.

1) PROVIDE SOILS REPORT FOR REVIEW.
2) STRUCTURAL ENGINEER SHALL STAMP THE SITE PLAN ACKNOWLEDGING LOCATION OF WALL.
3) SPECIAL INSPECTION SHALL BE REQUIRED FOR STRUCTURAL MASONRY. SPECIAL INSPECTION FORM NEEDS TO BE PROVIDED BEFORE PERMIT WILL BE ISSUED.
4)CLARIFY/JUSTIFY 4" BLOCK WALL IS ADEQUATE. PROVIDE A DESIGN. RETAINING WALL HAS BEEN JUSTIFIED IT CAN RESIST THE MOMENTS, BUT THE 4" FENCE HAS NOT BEEN JUSTIFIED.