Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL-BLDG/FIRE/ZONING/ENG
Permit Number - T06BU00383
Review Name: COMMERCIAL-BLDG/FIRE/ZONING/ENG
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 02/22/2006 | MARTIN BROWN | FIRE | REVIEW | Approved | |
| 03/15/2006 | RAUL PALMA | BUILDING-COMMERCIAL | REVIEW | Denied | City of Tucson, Development Services BUILDING AND STRUCTURAL COMMENTS 3/15/06 1) Provide a schematic diagram showing the joint coordinates and also the member labels. 2) Translate the data for the member sizes shown on calcs (sheet 9) to those on plans. For example, no. 27, M29,1/4 diam…how does this relate to plan sheet 2 of 2 on the details shown? Provide a summary showing how it all relates. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 03/21/2006 | AOLIVO1 | OUT TO CUSTOMER | Completed |
| 03/21/2006 | SUE REEVES | REJECT SHELF | Completed |