Permit Number: T06BU00279
Parcel: 140420150

Address:
2660 E MEDINA RD

Review Status: Completed

Review Details: GRADING

Permit Number - T06BU00279
Review Name: GRADING
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/07/2006 PETER MCLAUGHLIN ZONING REVIEW Denied Approved site plan required prior to grading plan approval.
03/10/2006 LOREN MAKUS ENGINEERING REVIEW Denied March 10, 2006
TO: Bruce Call. AECM
SUBJECT: Grading Plan: Marriott Residence Inn - Airport
REVIEWER: Loren Makus
ACTIVITY NUMBER: T06BU00279

SUMMARY: The Grading Plans were reviewed by Development Services Department, Engineering Division on December 2, 2005. They were not approved at this time.
1. The site plan must be approved before the grading plans can be approved.
2. In the Building Plan Sheet A9.4 Detail 10 indicates that the downspouts will be directed to the storm sewer. The storm sewer must be shown on the Grading Plan and addressed in the Drainage Report. Otherwise, revise the detail to show how the downspouts will discharge. Show how the discharge will not be directed over the sidewalks. If scuppers are used under the sidewalk show them on the grading plan.
3. Provide general dimensions for all of the basins and other drainage features. This is necessary so the inspectors can effectively inspect the site. They often must use photo-reproductions that are not scaleable.
4. Show how stormwater harvesting will be maximized.
5. The SWPPP and Notice of Intent must be signed by an operator.

If you have any questions or if you wish to discuss any of these comments, I can be reached at 520.791-5550 ext. 1161 or by email at loren.makus@tucsonaz.gov.
Loren Makus, E.I.T.
Senior Engineering Associate
Engineering Division
Development Services
03/10/2006 ANDREW CONNOR NPPO REVIEW Denied Approved site plan required prior to grading plan approval.

Final Status

Task End Date Reviewer's Name Type of Review Description
03/24/2006 GBONILL1 REJECT SHELF Completed