Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL-BLDG/FIRE/ZONING/ENG
Permit Number - T06BU00229
Review Name: COMMERCIAL-BLDG/FIRE/ZONING/ENG
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 02/01/2006 | DOUG LAAKSO | BUILDING-COMMERCIAL | REVIEW | Denied | .. T06BU00229 .. TCC NORTH EXHIBITION HALL ACOUSTICAL RETROFIT .. DGL .. 1ST REVIEW .. 2/3/06 .. S1. Provide Project Valuation. S2. Clarify accessibility per IBC Section 11 and 34 and ANSI A117.1-2003 ed, show where 20% of Project Valuation is spent on accessibility by noting on drawings what will be done and cost estimate showing amounts, if fully accessible note this on drawings . S3. Provide completed code review checklist. S4. Provide structural design for this project including : 1. Loads on and capacity of connections ref details on drawing A-5. 2. Structural capability of acoustical panels. 3. Tearout capacity of acoustical panels details 3/A-5 and 4/A-5.. 4. Tearout capacity of wire support detail 2/A-5. S5. Special inspection required for locating reinforcing of concrete structure. S6. Provide location plan showing where this building and the work to be done. S7. Provide 2nd set of building permit drawings Questions? Call Douglas Laakso Structural Plans Examiner for the City of Tucson Development Services Department at (520) 791-5550 x1111. |
| 02/01/2006 | JIM EGAN | FIRE | REVIEW | Approved |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 02/08/2006 | AOLIVO1 | OUT TO CUSTOMER | Completed |
| 02/08/2006 | SUE REEVES | REJECT SHELF | Completed |