Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/07/2006 ANDREW CONNOR NPPO REVIEW Denied 1. Submit stamped approved NPP plan included with approved tentative plat Case # S00-023. Review will continue upon re-submittal of approved documents.

2. Include the locations and designation of all TOS and PIP saguaros on the grading plan identical to approved NPP plan.
02/17/2006 LOREN MAKUS ENGINEERING REVIEW Denied February 22, 2006
T06BU00190
Grading Review by Loren Makus, E.I.T.

The grading plan cannot be approved at this time. This submittal of the grading plan was not reviewed for the Floodplain Use Permit and Watercourse channel revision. Any changes to the associated plans must be reflected on this plan. In addition the following comments must be addressed.
1. Clarify the nature of the rip rap that will be placed on the slopes. Indicate whether it will be grouted, hand placed or dumped. Indicate the required average rock size and thickness of the rip rap.
2. In accordance with the project SWPPP, show the locations and specifications for erosion and sediment controls on the grading plan.
3. Provide general dimensions for the driveways and fill areas for the project.
4. Provide a geotechnical report supporting the cut slope steeper than 1V:2H.
5. Clarify in the plan view and in detail A-A the location and extent of the interceptor trench and gutter. Clearly indicate the endpoints of the trench and gutter and fully describe the discharge location.
6. Provide a detail of the interceptor swale at the top of the cut slope at the north and west grading limits.
7. Clarify the use of keynote 5. The note appears on the list but is not used on the plan view.
03/09/2006 DROBEY1 ZONING REVIEW Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
03/09/2006 DELMA ROBEY OUT TO CUSTOMER Completed