Permit Number: T06BU00188
Parcel: 116094180

Address:
3156 W SALVIA DR

Review Status: Completed

Review Details: GRADING

Permit Number - T06BU00188
Review Name: GRADING
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/07/2006 ANDREW CONNOR NPPO REVIEW Denied 1. Submit stamped approved NPP plan included with approved tentative plat Case # S00-023. Review will continue upon re-submittal of approved documents.

2. Include the locations and designation of all TOS and PIP saguaros on the grading plan identical to approved NPP plan.
02/17/2006 LOREN MAKUS ENGINEERING REVIEW Denied February 22, 2006
T06BU00188
Grading Review by Loren Makus, E.I.T.

The grading plan cannot be approved at this time. This submittal of the grading plan was not reviewed for the Floodplain Use Permit and Watercourse channel revision. Any changes to the associated plans must be reflected on this plan. In addition the following comments must be addressed.
1. In accordance with the project SWPPP, show the locations and specifications for erosion and sediment controls on the grading plan.
2. Provide general dimensions for the driveways and fill areas for the project.
3. Provide a geotechnical report supporting the cut slope steeper than 1V:2H.
4. Provide a detail of the interceptor swale at the toe of the cut slope.
5. Remove the extraneous callout for detail A-A that appears in the roadway.
03/09/2006 DROBEY1 ZONING REVIEW Denied