Permit Number: T06BU00133
Parcel: Unknown

Address:
4050 E BENSON HY

Review Status: Completed

Review Details: GRADING

Permit Number - T06BU00133
Review Name: GRADING
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/31/2006 ANDREW CONNOR NPPO REVIEW Denied Submit stamped approved tentative plat including landscape and NPP plans, review will continue upon re-submittal of requested documents.
02/02/2006 ELIZABETH EBERBACH ENGINEERING REVIEW Denied DATE: February 6, 2006
SUBJECT: Cantera S05-030 Stockpile Grading Plan submittal Engineering Review
REVIEWER: Elizabeth Eberbach
ACTIVITY NUMBER: T06BU00133
LOCATION: T15S R14E Section 10

SUMMARY: The Stockpile Grading Plan, SWPPP documents, NPPO and Landscaping documents were received by Engineering on January 20, 2006. Engineering Division has reviewed the received items and is unable to provide a conditional approval of the stockpile and does not recommend approval of the Grading Plan at this time. Please address the following comments.

GRADING PLAN COMMENTS:
1) DS Sec.2-03.5.2: Provide 1 copy of the approved Tentative Plat or a copy of the latest Tentative plat.
2) DS Sec.11-01.8.3: Provide a copy of the soils report and a letter regarding geotechnical recommendations for height of stockpile, side slopes, and any other recommendations such as benching. Fills over 6-8 feet typically need assessment due to safety considerations.
3) Tucson Code 26-42(D): Floodplain encroachment will not be approved at this time. Address the following:
a) Submit a complete Drainage Report, if existing floodplain limits are not shown on the Tentative Plat.
b) Depict 100-year floodplain limits on planview of grading plan and SWPPP.
c) Revise grading plan and SWPPP to reflect no encroachment in the 100-year floodplain. Provide a cross section(s) along the north side of the stockpile to depict sufficient setback from floodplain to show no encroachment into the 100-year floodplain limits; show area for setback to include grading limits, stormwater controls, dimensioned width of vehicle access, and stockpile slope/height.
d) A Floodplain use permit will not be required if there is no encroachment into the jurisdictional flow.
4) DS Sec.11-01.8.1.A.1-4: If the fill is placed within 100 feet of residentially zoned parcels, differential grading procedures will need to be followed.
5) DS Sec.11-01.4.F: Clarify any revised grading limits with dimensions from project boundary.
6) Address the following SWPPP comments:
a) Tucson Code 26-42(A): Provide seal on SWPP report.
b) Provide signatures for operator certifications. At minimum one certification will be necessary - see page 9 in the SWPP report. Additional SWPPP comments may be forthcoming for the overall project grading permit review.
7) DS Sec.11-01.2.3.B: Provide disturbance area in square feet on plan. A reseeding bond is required in order to pick-up the grading permit. The reseed bond amount is based on $0.05 per sqft disturbance.
8) For review by the other DSD sections, submit any required Landscape documents.

It may be necessary to pick-up the review package and address all comments. Upon resubmittal, provide 4 copies of the revised Stockpile Grading Plan, a copy of the soils report and geotechnical letter, a copy of the Tentative Plat, a complete copy of the Drainage Report, any landscape documents, and three copies of the updated SWPPP package. If you would like to set up a meeting to go over these comments, or to "walk through" the grading plan with Engineering at the counter, you may call me at 791-5550 extension 2204.

Elizabeth Eberbach, PE
Civil Engineer
Engineering Division
Development Services
02/09/2006 HEATHER THRALL ZONING REVIEW Denied Per Craig Gross, this project was denied. The tentative plat must be submitted with the project to allow for staff review.

Final Status

Task End Date Reviewer's Name Type of Review Description
02/09/2006 GBONILL1 OUT TO CUSTOMER Completed