Review Date Reviewer's Name Type of Review Description Status Comments
04/04/2006 RAUL PALMA BUILDING-COMMERCIAL REVIEW Denied 1) Special inspection required for pilaster.
2) Provide engineering calc`s for the 4" cmu wall portion.
3) Refer to TOE PRESSURE calc`s--show how all the numbers shown were obtained.(1113,640,1086) Provide
a sketch to demonstrate.
4) Provide complete detail(s) showing how the wall will
be put together, in particular at the pilaster.