Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T06BU00093
Parcel: 14101875A

Review Status: Completed

Review Details: COMMERCIAL-BLDG/FIRE/ZONING/ENG

Permit Number - T06BU00093
Review Name: COMMERCIAL-BLDG/FIRE/ZONING/ENG
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/19/2006 DOUG LAAKSO BUILDING-COMMERCIAL REVIEW Denied .. T06BU00093 .. 10431 E CAPERCAILLIE STREET .. DGL .. 1ST REVIEW .. 1/20/06 ..

S1. Provide completed code review checklist, see DSD website at Forms, www.tucsonaz.gov/dsd.
S2. Show accessible route on drawings, per International Building Code Section 11 and ANSI A117.1-2003ed :
1. Identify location of accessible route per IBC Sec 1104 and ANSI Sec 4.
2. Show accessibility to recreational facilities, including basketball court, pet waste station, council ring, ramada, grill, benches, other equipment provided per IBC Sec 1109.14.3.
3. Show location, dimensions and specifications for detectable warnings per IBC Sec 1109.9 and ANSI A117.1 Sec 705.
4. Specifications and location of accessible drinking fountain per IBC Sec 1109.5 and ANSI Sec 602.
5. Ramps, landings, slopes, grade changes and maneuvering clearances.
S3. Submit two sets of shop drawings and calculations, stamped and signed by an Arizona Registered engineer, shop drawings shall be reviewed by and bear the approval of the Engineer or Architect of Record prior to submission to the City of Tucson , Development Services Department for approval prior to erection for the Ocotillo Ramada.

Questions? Call Douglas Laakso Structural Plans Examiner for the City of Tucson Development Services Department at (520) 791-5550 x1111
02/03/2006 CAGUILA1 ZONING REVIEW Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
02/03/2006 CINDY AGUILAR OUT TO CUSTOMER Completed