Permit Number: T06BU00043
Parcel: 12908021G

Address:
1239 S CHERRY AV

Review Status: Completed

Review Details: RESUBMITTAL - GRADING

Permit Number - T06BU00043
Review Name: RESUBMITTAL - GRADING
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/24/2006 PATRICIA GILBERT ENGINEERING REVIEW Denied DATE: April 24, 2006
ACTIVITY NUMBER: T06BU00043
PROJECT NAME: The Bottle Shop
PROJECT ADDRESS: 1239 South Cherry Avenue
PROJECT REVIEWER: Patricia Gilbert

The following items must be revised or added to the grading plan. Please include a response letter with the next submittal that states how all comments have been addressed.

RESUBMITTAL REQUIRED: 4 COPIES OF THE GRADING PLAN AND SWPPP

APPROVED: DRAINAGE STATEMENT

APPROVED: STORMWATER POLLUTION PREVENTION PLAN

1. A copy of the stamped approved Site Plan must be included with the Grading Plan submittal.

2. The Site Plan is currently in review. Any changes made to the Site Plan must be reflected on the Grading Plan. The Site Plan and Grading Plan must match.

3. Provide a cross section detail through the landscape border. Include the ROW and the Building. Provide appropriate dimensions and label accordingly. If curb and sidewalk are located within the ROW include in the detail. (See comment 11)

The above comment is from the first review. It is acknowledged that a cross section detail has been provided on sheet 4. The request was made to include ROW information in the cross section. Detail 15 does not show any ROW information. Provide either on the plan view or in detail 15; the distance from the property line to the face of curb or the end of pavement, indicate if there is existing or proposed sidewalk, include the width. Revise appropriately.

SWPPP COMMENTS

1. Please submit 4 copies of the SWPPP with the next submital.
04/25/2006 ANDREW CONNOR NPPO REVIEW Approved
05/02/2006 AKLAPPE1 ZONING REVIEW Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
05/02/2006 AMERY KLAPPERT OUT TO CUSTOMER Completed