Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

The login landing page when selecting 'View' is still occurring and is still pending further investigation. 

Permit Number: T05PL01375
Parcel: 12404003B

Address:
1420 E 1ST ST

Review Status: Completed

Review Details: PLUMBING

Permit Number - T05PL01375
Review Name: PLUMBING
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/24/2005 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Provide a trap and vent for the pre-rinse sink. Reference Section 1011.5, UPC 1994.
2. Provide a grease trap of at least 20 GPM capacity and install per the manufacturer's instructions. Reference Section 1011.2, UPC 1994.
3. Install the flow control device on the inlet side of the grease trap. Reference Section 1011.3, UPC 1994.