Permit Review Detail
Review Status: Completed
Review Details: PLUMBING
Permit Number - T05PL01375
Review Name: PLUMBING
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 08/24/2005 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Provide a trap and vent for the pre-rinse sink. Reference Section 1011.5, UPC 1994. 2. Provide a grease trap of at least 20 GPM capacity and install per the manufacturer's instructions. Reference Section 1011.2, UPC 1994. 3. Install the flow control device on the inlet side of the grease trap. Reference Section 1011.3, UPC 1994. |